Application
Voltage |
230/415 VAC |
Configuration |
3Ø /4 Wire |
Characteristics
Fusing |
Internal |
Indication |
Blue LEDs On / Red LEDs Off |
Conductor |
12 AWG Stranded |
Enclosure |
NEMA Type 4X |
Certifications
Listing |
ANSI/UL 1449 Ed. 3 / IEC 61643-11 |
Environmental |
RoHS |
Diagram

Specifications
Modes of Protection |
L-N, L-L |
Type (Class) |
2 (2) |
Clamp Voltage [1 mA] L-N (L-L) |
510 (1020) |
VPL [2kA] L-N (L-L) |
900 (1600) |
VPR [3kA] L-N (L-L) |
1200 (2000) |
SCCR |
100 kA |
MCOV L-N (L-L) |
300 (600) |
Operating Temperature |
-40C to 85C |
Operating Humidity |
1% to 95% |
Filtering |
UL 1283 |
EMI-RFI Noise Attenuation |
< 40 db |
Capacitance |
1 to 1.5 uF / Line |
Component Response Time |
< 1 ns |
Frequency Range |
50 - 400 HZ |
Standard Installation Summary