Application
Voltage |
120/240 VAC |
Configuration |
3 Ø /4 Wire [Hi-Leg] |
Characteristics
Fusing |
Internal |
Indication |
Blue LEDs On / Red LEDs Off |
Conductor |
12 AWG Stranded |
Enclosure |
NEMA Type 4X |
Certifications
Listing |
ANSI/UL 1449 Ed. 3 / IEC 61643-11 |
Environmental |
RoHS |
Diagram

Specifications
Modes of Protection |
L-N, L-L |
Type (Class) |
2 (2) |
Clamp Voltage [1 mA] L-N (L-L)[Hi-Leg] |
220 (440) [510] |
VPL [2kA] L-N (L-L) [Hi-Leg] |
500 (960) [900] |
VPR [3kA] L-N (L-L) [Hi-Leg] |
700 (1000) [1200] |
SCCR |
100 kA |
MCOV L-N (L-L) [Hi-Leg] |
140 (280) [300] |
Operating Temperature |
-40C to 85C |
Operating Humidity |
1% to 95% |
Filtering |
UL 1283 |
EMI-RFI Noise Attenuation |
< 40 db |
Capacitance |
1 to 1.5 uF / Line |
Component Response Time |
< 1 ns |
Frequency Range |
50 - 400 HZ |
Standard Installation Diagram
.png)
MAXIVOLTSerious Surge Protection®
GuardDog®
Made in the
USA
Download Data Sheet
View Our Catalog